XRSuper6/XR20/XR40 Installation Guide Digital Monitoring Products
15
ComplIanCe
ANSI/UL 1023 Specications
Household Burglar-Alarm System Units
16.1 Bell Cutoff
The bell cutoff time cannot be less than ve minutes. See the XRSuper6/XR20/XR40 Programming Guide
(LT-0305).
16.2 Entry Delay
The maximum entry delay used must not be more than 45 seconds. See the XRSuper6/XR20/XR40
Programming Guide (LT-0305).
16.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the Programming Guide (LT-0305).
16.4 Zone Expansion on 4-Wire Bus
When expansion zones are used, the keypad and zone expander 4-wire bus must be limited to three feet
in length unless an external communication fail indicator is added. A 12 VDC relay may be wired as a
communication fail indicator. To install, connect the negative side of the indicator to one of the panel’s
annunciator outputs and the positive side to the smoke power (terminal 11 of the panel). See the XRSuper6/
XR20/XR40 Programming Guide (LT-0305).
In addition to the wiring described above, a 24-hour zone must be programmed to activate the appropriate
annunciator output.
16.5 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1103 must be programmed Normally Closed. See the
XRSuper6, XR20, XR40 Programming Guide (LT-0305).
16.6 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero). See the XRSuper6, XR20, XR40
Programming Guide (LT-0305).
16.7 Wireless Audible Annunciation
The Wireless Audible option must be selected as DAY for residential applications.
ANSI/UL 1610 and ANSI/UL 1076 Specications
Central-Station and Proprietary Burglar-Alarm Units
17.1 Opening/Closing Reports
The Opening/Closing Reports option must be programmed as YES. See the Programming Guide (LT-0305).
17.2 Automatic Bell Test
This option must be programmed as YES. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
17.3 Proprietary Dialer
The Model XRSuper6/XR20/XR40 provide proprietary service when congured as a digital dialer.
17.4 Standard Line Network Security
Standard Line Security is provided when congured as a NET system using an XRSuper6, XR20, or XR40 panel
with an iCOMSL™ Network Alarm Router. The NET Check-in time must be set from 01 to 06 minutes. When a
dialer is required for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A) is required.
When the check-in time is set to a number less than 200 seconds (1, 2, or 3 minutes), an attack resistant
enclosure is not required. See the Communication section of the XRSuper6, XR20, XR40 Programming Guide
(LT-0305).
17.5 Wireless Arming Mode
The System Options Mode for arming must be programmed as Area or All/Perimeter (A/P). See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
17.6 Wireless Tamper
The Zone Information Disarmed Open Message to Transmit must be programmed Trouble (T). See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
17.7 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1103 must be programmed Normally Closed. See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).