LT-0401 1.06 © 2014 Digital Monitoring Products, Inc.
INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
800-641-4282
www.dmp.com
Designed, Engineered
and Assembled in U.S.A.
Springeld, Missouri 65803-8877
14035
Wiring Specications for Keypad and LX-Bus
1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do Not use twisted
pair or shielded wire for LX-Bus and keypad bus data circuits. To maintain auxiliary power integrity when
using 22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. Install an
additional power supply to increase the wire length or add devices.
2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance
can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet.
As wire distance from the panel increases, DC voltage on the wire decreases.
3. Maximum number of devices per 2,500 feet circuit is 40.
Note: Each panel allows a specic number of supervised keypads. Add additional keypads in the unsupervised
mode. Refer to the panel installation guide for the specic number of supervised keypads allowed.
4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage
at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When
voltage is too low, the devices cannot operate properly.
For additional information refer to the panel installation guide and LX-Bus/Keypad Bus Wiring Application Note
(LT-2031) or the 710 Installation Guide (LT-0310).
Compliance Listing Specications
UL
To comply with ANSI/UL 365 Police-Connected Burglary System or ANSI/UL 609 Local Burglary Alarm Systems, the
module must be mounted in the supplied, UL listed enclosure with a tamper.
Any power supply used in a re listed installation must be regulated, power limited, and listed for Fire Protective Signaling.
ULC Commercial Burglary (XR100/XR500 Series or XR150/XR350/XR550 Series Panels)
A DMP Model 307 Clip-on Tamper Switch programmed as a 24-Hour zone is required on the zone expander enclosure.
The 714/715 zones can be installed in Medium or High Risk applications when two zones are used as shown in the Dual
Zone Protection diagram in the XR100/XR500 or XR150/XR350/XR550 Canadian Installation guides. Otherwise, 714/715
zones can only be used in Low Risk Applications.
ULC Residential Fire
Refer to the table below for ULC approved 2-Wire Smoke Detectors. Refer to the panel installation guide for the
complete list of UL approved smoke detectors.
Manufacturer Model Detector ID DC Voltage Range # of Detectors
Sentrol/ESL 528B, 528BXT S09A 6.5-20 12
Specications
Operating Voltage 8.8 to 15.0 VDC
Operating Current
714-8/16
Average 20mA + 1.6mA per zone
Alarm 20mA + 2mA per zone
715-8/16
Average 20mA + 4mA per zone
+ 0.1 per 2-wire smoke
Alarm 20mA
+ 58mA per shorted zone
+ 0.1 per 2-wire smoke
+ 30mA per smoke in alarm
Enclosure Specications
Enclosure 20-Gauge cold-rolled steel
Dimensions 12.5” W x 11.5” H x 3.5” D
714-8/-16 Color Gray
715-8/-16 Color Red
Compatibility
XT30/XT50 Series panels
XR100/XR500 Series panels
XR150/XR350/XR550 Series panels
Listings and Approvals
California State Fire Marshal (CSFM)
New York City (FDNY COA #6123)
New York City 1100 Series Wireless (FDNY COA #6145)
Underwriters Laboratories (UL) Listed
ANSI/UL 365 Police Station Connect Burglar Alarm Systems
ANSI/UL 609 Local Burglar Alarm Units & Systems
ANSI/UL 864 Fire Protective Signaling Systems
ANSI/UL 985 Household Fire Warning System Units
ANSI/UL 1023 Household Burglar Alarm System Units
ANSI/UL 1076 Proprietary Burglar Alarm Units & Systems
ANSI/UL 1610 Central Station Burglar Alarm Units
ANSI/UL 1635 Digital Alarm Communication System Units
Underwriters Laboratories Canada (ULC) Listed
ULC Subject-C1023 Household Burglar
ULC/ORD-C1076 Proprietary Burglar
ULC S304 Central Station Burglar
ULC S545 Household Fire
Komentáře k této Příručce