zone informaTion
19.9
NEXT ZN? NO YES
Next Zone
Select YES to terminate zone programming. The display returns to Zone Number,
allowingyoutoenteranewzonenumber.SelectNOtomakealterationstothe
AlarmActionforazone.AlarmActionisdenedbeginningwithsection16.12.
Toprogramzonesforwirelessoperation,selectNOattheNEXTZONE-NOYES
option.TheWIRELESSNOYESoptiondisplays.Ifthezoneyouareprogramming
isintendedforwirelessdevices,selectYES.SelectNOtocontinueprogramming
non-wirelesszonesinthe500to999range.
• Zones400to449canbeprogrammedfor1100SeriesKeyFobs.
• Zones500to699canbeprogrammedforFASeriesWireless.
• Zones500through999canbeprogrammedforDMP1100SeriesWireless.
DMP Wireless
For a DMP 1100X Wireless Receiver set the House Code from 1 to 50. See House Code programming in
SystemOptions.Zones500through999canbeprogrammedasWirelesszones.SettheXR500Seriespanel
J23jumpertoXtoenableon-boardDMPWirelessoperation.BrieyresetthepanelusingtheJ16jumper
toactivateWirelessoperation.RefertotheXR500SeriesInstallationGuide(LT-0681).
For an 1100 Series Key Fob see section 19.11.
For an FA Series Remote Wireless Receiver see section 19.12.
NOTE: AllwirelessprogrammingisstoredintheXR500Seriespanel.The1100XWirelessReceiverobtains
the necessary programming information from the panel each time the receiver powers up, when the
programmerSTOProutineisselectedorthepanelisreset.Thereceivermemoryrefreshtakesupto10
secondstocompletedependingonthenumberofwirelesszonesprogrammedandtheRedLEDremainson
during this time. Normal receiver operation is inhibited during the memory refresh period.
19.10 Wireless
Select YES to program this zone as a DMP wireless zone. You must program
the wireless House Code prior to adding DMP wireless zones to the system. See
HouseCodeprogramminginSystemOptions.DefaultisNO.
19.10.1
TRANSMITTER
SERIAL#: XXXXXXXX
Serial Number Entry
Entertheeight-digitserialnumberfoundonthewirelessdevice.
ALREADY IN USE
ZONE NUMBER: XXX
This message displays when the serial number is already programmed for
another zone. The programmed zone number displays.
19.10.2
TRANSMITTER
CONTACT:XXXXXXXX
Contact
Thisoptiondisplaysiftheserialnumberenteredisforan1101or1103Universal
Transmitteror1114WirelessFour-ZoneExpander.Pressanytoprowkeyto
select the contact.
TRANSMTR CONTACT
INT EXT
Thisoptiondisplayswhenprogrammingan1101or1103Transmitter.SelectINT
to use the internal reed switch contacts. Select EXT to connect an external
devicetothe1101or1103terminalblock.DefaultisINTERNAL.
ByallowingbothoftheModel1101or1103transmittercontacts(INTand
EXT)tobeusedatthesametime,twozonesmaybeprogrammedfrom
onetransmitter.Whenusingbothcontacts,youmustuseconsecutivezone
numbers.Zones531and532orzones890and891areacceptablezone
assignments.
Forexample,programtransmitterserialnumber01345678asZone521with
an INT contact type and Zone 522 with an EXT contact type. The same serial
number is used for both zones.
Note:Whenusingthe1103UniversalTransmitterinaULlistedCommercial
Burglary installation, the external contact cannot be used.
ZONE INFORMATION
WIRELESS? NO YES