Digital Monitoring Products XR500 Series Programming Guide
6
InItIalIzatIon
Initialization
NOTE: WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN AND ‘SAVING
PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE PROGRAMMING CHANGES. SEE SECTION 17.1.
2.1
INITIALIZATION
Initialization
This function allows you to clear selected parts of the panel program back to the factory
defaults in preparation for system programming. Run the initialization function on all
new installations.
CODES?
NO YES
SCHEDS?
NO YES
Fo
r each section of the panel program you
can initialize, a NO or YES option is provided.
Selecting YES advances you to
a confirmation prompt.
If you select YES, the panel initializes that section of
the program and advances you to the next prompt.
If you select NO, the panel advances you to the next
section prompt but does not initialize that section of
the program.
SURE?
YESNO
Selecting NO adv
ances
you to the next prompt.
2.2
INIT ALL? NO YES
SURE? YES NO
Clear All Memory
NO - Leaves existing programming intact then displays Clear All Codes.
YES - Clears all memory then displays Reset Panel. Reset the panel by shorting J16 and
re-enter programming mode to continue.
2.3
CODES? NO YES
SURE? YES NO
Clear All Codes
NO - Leaves existing codes intact.
YES - Clears the user code and user prole memory and assigns user code number 99 to
the highest user position.
Note: The user name for the default user code is created using the current programmed
primary user language.
2.4
SCHEDS? NO YES
SURE? YES NO
Clear All Schedules
NO - Leaves existing schedules intact.
YES - Clears all shift, and output schedules.
2.5
EVENTS? NO YES
SURE? YES NO
Clear Display Events Memory
NO - Leaves existing event memory intact.
YES - Clears the events memory.
2.6
ZONES? NO YES
SURE? YES NO
Clear Zone Information
NO - Leaves existing zone information intact.
YES - Clears the zone information for all zones. All zones are marked * UNUSED * and
must be renamed before being able to display on any system keypad.
2.7
AREAS? NO YES
SURE? YES NO
Clear Area Information
NO - Leaves existing area information intact.
YES - Clears the area information for all areas. All areas are marked * UNUSED * and must
be renamed before being able to display on any system keypad.
2.8
OUTPUTS? NO YES
SURE? YES NO
Clear Output Information
NO - Leaves existing output information intact.
YES - Clears all programmed Output names and any output cutoff assignment.
2.9
COM/RMT? NO YES
SURE? YES NO
Clear Communication and Remote Options
NO - Leaves existing communication and remote options intact.
YES - Clears communication and remote options programming to factory defaults.
2.10
DEFAULTS NO YES
SURE? YES NO
Set to Factory Defaults
NO - Leaves existing panel programming intact.
YES - Sets the remainder of the panel programming back to the factory defaults.
Note: Sets the Programming and User language to English.