Digital Monitoring Products XR100 Series Installation Guide
16
INSTALLATION
XR100 Series Installation Guide Digital Monitoring Products
17
INSTALLATION
J23 6-Pin Header
14.1 Description
The XR100 Series Command Processor™ panel supports Direct Programming, LX-Bus, and, DMP Wireless operation.
These operations cannot function at the same time. Install a jumper on one pair of J23 headers to indicate how
the panel is programmed to operate. Refer to the table below when installing a jumper on J23. When a jumper
is installed or moved on the 6-pin header, briey reset the panel using the J16 jumper to activate the selected
operation.
Note: The Direct Programming, LX-Bus operation, and DMP Wireless operations cannot be used at the same time.
J23 6-pin Header
Letter Operation
R Direct Programming
L LX-Bus
X DMP Wireless
J22 LX-Bus Expansion Connector
15.1 Description
The XR100 Series Command Processor™ Panel supports one LX-Bus circuit that provides 100 expansion zones, DMP
Wireless that provides 100 wireless zones, or direct connect programming. Enable J22 LX-Bus Header to use the 100
expansion or wireless zones.
15.2 J22 LX-Bus Header
Note: The LX-Bus, DMP Wireless, and Direct Programming operations cannot be used at the same time.
For each connection, respect wire colors when connecting devices and use all four wires. After placing the jumper
on the J23 6-Pin header to enable the required operation, briey reset the panel using the J16 jumper to activate
operation.
Wireless Bus Operation: Place a jumper on the two pins next to the letter “X” on the J23 6-Pin header. When using
J22 as a wireless bus, connect a DMP Model 300 4-wire Harness to the J22 4-pin header labeled LX. Connect the
other end to the J3 header on the 1100X Wireless Receiver. This provides up to 100 wireless zones numbered 500 to
599. Refer to the 1100X Wireless Receiver Install Guide (LT-0708).
LX-Bus Operation: Place a jumper on the two pins next to the letter “L” on the J23 6-pin header. When using J22
as an LX-Bus, connect a DMP Model 300 4-wire Harness to the J22 6-pin header labeled LX. This provides 100 LX-Bus
zones numbered 500-599.
Note: Do NOT use shielded wire when using the LX-Bus.
Direct Programming Operation: Place a jumper on the two pins next to the letter “R” on the J23 6-Pin header.
When using J22 as a direct programming port, connect a the 4-wire connector from DMP Model 399 Harness to the
J22 4-pin header labeled LX. Connect the Model 399 DB-9 connector onto an RS-232 port on a Laptop computer.
This allows direct panel programming from the attached computer.
15.3 LX-Bus LEDs
The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The top LED
ashes green to indicate the panel is transmitting LX-Bus data. The bottom LED ashes yellow to indicate the panel
is receiving LX-Bus data.
15.4 OVC LED
The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw more
current than the panel is rated for. The OVC is located above Outputs 1 and 2 on the panel and turns a steady Red
when lit. When the OVC LED lights Red, the LX-Bus(es) and Keypad bus shut down.
Figure 6: J23 6-pin Header
LEDs
Xmit
Receiv
e
J22
LX
Overcurrent
LED
J2
3
R
L
X