System Link User’s Guide
80
Acknowledging an Alarm
The bottom right corner of the Alarm List contains six buttons to use when responding to an
alarm message. System Link records all alarm acknowledgement, removal, and disable
actions in an activity database log.
Note: No action is taken on a message until an operator has logged in.
Ack – F6
: Click this button to acknowledge an alarm. Acknowledging an alarm silences the
warning tone on the computer, unless there are additional unacknowledged alarm
messages. You may also acknowledge alarms by pressing the F6 key.
Note: A message cannot be acknowledged until an operator has logged in.
Acknowledging an alarm message also changes the message background color from violet to
the color designating the alarm type (see page
772). Acknowledging an alarm only
indicates that you are aware of the message. It does not silence any notification
appliances triggered by the panel.
Remove – F9
: Click this button to remove an alarm from the alarm list. A pop-up window
appears asking if you are certain that you wish to remove the alarm message. Select Yes
or No.
Note: A message cannot be removed until an operator has logged in.
Selecting Yes deletes the message from the Alarm List. A message must be acknowledged
before it can be removed.
Selecting No cancels the message removal and leaves the message in the Alarm List.
Disable – F12
: Click this button to disable the selected message and move it from the
Alarm List to the Disabled List. When disabling a message a pop-up window appears, asking
if you are certain you want to disable the alarm message. You may also disable a message
by pressing the F12 key. All disabled alarm messages are placed in the Disabled List.
Note: A message cannot be disabled until an operator has logged in.
Selecting Yes moves the message from the Alarm List to the Disabled List. A message must
be acknowledged before it can be disabled.
Selecting No cancels the action and leaves the message in the Alarm List.
Note: When a signal is received from a panel and an operator has not logged in to System
Link, and the program is running on the computer, the Alarm List window opens. In
addition, a pop-up window opens with the message “Operator must log on before
processing message.”
A message may not be acknowledged until an operator has logged in to System Link.