Digital Monitoring Products XR100 Series Canadian Installation Guide
2
IntroductIon
2.2 Zone Expansion
Upto142additionalzonesareavailableontheXR100SeriesusingDMPLCDkeypadremotezonecapabilityandzone
expansion modules. The panel keypad data bus supports up to eight supervised device addresses with each address
supporting up to four programmable expansion zones.
Upto100zonesareavailableusingtheonboardLX-Bus,Model481,462Nand464-263H,andanycombinationofsingle,
four, eight, or 16-zone expansion modules and single-zone LX-Bus™ detectors.
Note:DonotuseshieldedwireforLX-BusorKeypadBuscircuits.
2.3 Output Expansion
In addition to the two SPDT relays and four programmable open collector outputs on the XR100 Series, you can also
connect up to 25 programmable Model 716 Output Expansion Modules. These modules can provide an additional 100
programmable SPDT relays.
The XR100 Series provides 100 Output Schedules for programming the 716 to perform a variety of annunciation and control
functions. Also assign the 716 outputs to any panel Output Options such as Fire Alarm, Communication Fail, or Phone
TroubleOutputs.Refertothe716InstallationGuide(LT-0183).
TheLX-Bus™alsosupportstheModel717GraphicAnnunciatorModule.Each717modulesupplies20switchedground
outputs that follow the state of their assigned zones.
Note:The717supportsthersteightKeypadBusaddresses.Refertothe717InstallationGuide(LT-0235)and716
InstallationGuide(LT-0183).
2.4 Central Station Communication
Program the XR100 Series panel for reporting to DMP SCS-1R or SCS-VR Receivers using digital dialer, cellular, network, or
Contact ID communication. The XR100 Series connects at the premises to a standard RJ31X or RJ38X telephone jack. Use
the DMP 893A Dual Phone Line Module when connecting the XR100 Series panel to two separate phone lines.
2.5 Caution Notes
Throughout this guide you will see caution notes containing information you need to know when installing the panel. These
cautionsareindicatedwithayieldsign.Wheneveryouseeacautionnote,makesureyoucompletelyreadandunderstand
its information. Failing to follow the caution note can cause damage to the equipment or improper operation of one or
more components in the system. See the example shown below.
Always ground the panel before applying power to any devices: The panel must be properly grounded
before connecting any devices or applying power to the panel. Proper grounding protects against Electrostatic
Discharge (ESD) that can damage system components.
2.6 Compliance Instructions
For applications that must conform to a local authorities installation standard or a National Recognized Testing Laboratory
certicatedsystem,pleaseseetheListedComplianceSpecicationssectionneartheendofthisguideforadditional
instructions.
System Components
3.1 Description
The DMP XR100 Series system is made up of an alarm panel with a built-in communicator, an enclosure, battery, one 16.5
Vac transformer, and keypads. You can use up to sixteen supervised 32-character LCD keypads; network communications;
zone and output expansion modules; and initiating and indicating circuit modules. You can also connect auxiliary devices
to the panel’s output relays to expand the basic system control capability. Combined current requirements of additional
modules may require an auxiliary power supply. Refer to the XR100 Series Power Requirements section in this guide when
calculating power requirements.