Digital Monitoring Products XR150/XR350/XR550 Series Programming Guide
32
OUTPUT OPTIONS
11.19 Supervisory Alarm Output
Enter the output/Favorite number to turn on when a supervisory zone type is placed into
an alarm. The output turns off when all supervisory type zones are restored to normal.
Enter 0 (zero) to disable. Default is 0.
11.20 Heat Saver Temperature
Enter the desired temperature setting for all Z-Wave thermostats when the system
is armed ALL or AWAY. When the system is disarmed the thermostats return to their
previous settings. The range is 55-95 degrees. Enter 0 (zero) to disable.
11.21 Cool Saver Temperature
Enter the desired temperature setting for all Z-Wave thermostats when the system
is armed ALL or AWAY. When the system is disarmed the thermostats return to their
previous settings. The range is 55-95 degrees. Enter 0 (zero) to disable.
SUPV ALM OUT: 0
HEAT SAVER
TEMPERATURE: 0
COOL SAVER
TEMPERATURE: 0