XR150/XR350/XR550 Series Programming Guide Digital Monitoring Products
51
ZONE INFORMATION
STEADY - The output is turned on and remains on until the area is disarmed, an output
cutoff time expires, or the output is reset from the keypad menu.
PULSE - The output alternates one second on and one second off.
Note: The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off normal, or
bad condition. When the zone restores, the output is turned off.
Note: For Day Zone types, when an output is turned on, a user code with silence
authority can turn the output off.
After you make the three selections in the sections above, the display prompts for the
same three selections for Disarmed Short, Armed Open, and Armed Short conditions. If
the zone is a 24-hour type, only the Armed Open and Armed Short conditions display.
When you have programmed all of the zone conditions, the Swinger Bypass selection
then dis plays.
18.17 Swinger Bypass
Selecting YES allows the zone to be swinger bypassed by the panel according to the
specications pro grammed in Swinger Bypass Trips and Reset Swinger Bypass. The Bypass
condition displays in the keypad Status List. Selecting NO disables swinger bypassing for
this zone.
How it works
If within one hour, a zone trips the total number of times as specied in Swinger Bypass
Trips, the panel bypasses it until the following conditions occur; the area in which the
zone is assigned is disarmed, the zone is manually reset through the Bypass Zones?
keypad User Menu function, the zone remains normal for one hour and the Reset Swinger
Bypass is YES.
If the zone trips fewer than the specied times within one hour, the bypass trip counter
returns to 0 (zero) and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
18.18 Prewarn Keypad Addresses
At the entry delay start, all keypad addresses selected here dis play ENTER CODE:-. If
you want the prewarn to sound at all 16 addresses, leave the default setting.
To delete an address, press the matching number on the keypad. To disable prewarning
at all keypads, press a top row Select key to clear the addresses shown. Press the COM-
MAND key when the address selection is com plete.
The prewarn tone stops at the keypad where the rst user code digit is entered. If no
keys are pressed for ve seconds or an invalid user code is entered, the prewarn tone
resumes at that keypad.
18.19 Entry Delay
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System Options.
18.20 Zone Retard Delay
When you select YES, the zone operates with the zone retard delay. The retard func tions
only in zone short condi tions.
The zone must re main shorted for the full length of the re tard de lay before the panel
recognizes its condition. If you select NO, the zone operates without a retard delay.
18.21 Presignal Keypad Addresses
You can enable any combina tion of keypad addresses to sound a presignal tone during
the time a zone is in retard delay. The presignal tone si lences when the zone restores or
the re tard delay expires.
To en able a presignal ad dress, press any top row Select key followed by the number of
the keypad address. You can enable the presignal for all 16 keypad addresses. To disable
a presignal address press the matching number digit again. Press the COMMAND key
when the address selection is complete. The Presignal option is only displayed when
Retard is selected as YES.
18.22 Fast Response
Select YES to provide a zone response time of 167ms. Select NO to provide a normal
zone response time of 500ms. Zones 500 to 999 have a xed response time and do not
display this option.
STD PLS MOM FOLW
SWGR BYP NO YES
PREWARN KEYPADS:
ENTRY DELAY: 1
RETARD NO YES
PRESGNL KEYPADS:
FAST RSP NO YES