Digital Monitoring Products XTL/XTLC Programming Guide
26
ZONE INFORMATION
This option displays when programming an 1114 zone expander which provides four input
contacts. Press any top row key to select the contact. Default is Contact 1.
Select the contact number to program. The same transmitter serial number is used for
all four contacts. When using the contacts, you must use consecutive zone numbers.
For example, use serial number 08345678 to program Contact 1 for Zone 21, Contact 2
for Zone 22, Contact 3 for zone 23, and Contact 4 for zone 24.
A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.
This message displays when the Contact is already programmed for another zone. The
programmed zone number displays.
The Normally Open option only displays when EXT is selected as the Contact type. For
external devices connected to the 1101 terminal block, select NO to use normally closed
(N/C) contacts. Select YES to use normally open (N/O) contacts. Default is NO.
13.10.1 Supervision Time
Press any top row key to select the supervision time required for the wireless zone. Press
COMMAND to accept the default time. Default is 240 minutes.
Select the required number of minutes. The transmitter must check in at least
once during this time or a missing condition is indicated for that zone. 1100 Series
transmitters automatically checkin based on the supervision time selected for the
wireless zone, no additional programming is needed. If two zones share the same
transmitter, the last programmed supervision time is stored as the supervision time for
both zones. Zero (0) indicates an unsupervised transmitter.
The 3 minute supervision time is only available for zone types of Fire (FI), Fire Verify
(FV), and Supervisory (SV).
Note: When the panel is reset or a receiver is installed or powered down and powered
up, the supervision timer restarts for all wireless zones.
13.10.2 LED Operation
This only displays when programming a panic or pendant transmitter. Select YES to turn
a panic or pendant LED on during normal operation. Select NO to turn the LED off during
normal operation. The LED always operates on all transmitters when the transmitter
case is open and the tamper is faulted. Default is YES.
13.10.3 Disarm/Disable
Select YES to disable the zone tripped message from an 1103 Universal Transmitter
(Version 107 or higher software) or 1126/1127 PIRs during the disarmed period. When
disarmed, the transmitter or PIR only sends supervision, tamper, and low battery
messages to extend transmitter battery life. For 1103 Transmitters, a zone tripped
message is sent if the zone remains tripped for 20 seconds. Select NO to always send
zone tripped messages in addition to supervision, tamper, and low battery.
Default is YES.
13.10.4 Wireless PIR Pulse Count
Select the number of infrared pulse counts (2 or 4) the PIR will use before sending a
short message. The rst infrared pulse starts a timer and count. If no additional infrared
pulses occur in 25 seconds, the timer and count are reset. Default is 4.
13.10.5 Wireless PIR Sensitivity
Select the sensitivity setting for the PIR. Selecting LOW sets the PIR to operate at
75% sensitivity for installations in harsh environments. Selecting HIGH sets the PIR to
maximum sensitivity. Default is LOW.
13.10.6 Next Zone
Select YES to return to the ZONE NO: - option to program a new zone. Select NO to
display the Alarm Action option.
CONTACT: x
1 2 3 4
ALREADY USED Zxx
NORM OPEN NO YES
SUPRVSN TIME: XX
0 3 60 240
LED OPER NO YES
DISARM DISABLE
YES
WIRELESS PIR
PULSE COUNT:
4
WIRELESS PIR
SENSITIVITY: LOW
NEXT ZN NO YES