XTL/XTLC Programming Guide Digital Monitoring Products
31
ZONE INFORMATION
If no other cross-zoned zone in the system trips before the cross-zone time expires, the
panel sends only a fault report from the rst zone to the receiver.
Note: If CRS ZONE is YES, a valid CRS ZN TIME must be programmed in System Options
for this feature to be enabled.
Cross-zoning is not compatible and cannot be enabled for Fire Verify zone types.
13.18 Priority
Selecting YES allows you to provide additional protection for a zone by requiring it to be
in a normal condition before its assigned area can be armed. A priority zone cannot be
bypassed.
A Priority zone not in a normal condition cannot be armed. If a user attempts to arm
the area, the keypad displays the bad zone name followed by PRIORITY ZONE and the
arming is stopped.
13.19 TrafcCount
This option is displayed for NT or EX type zones. Select YES to provide reporting to the
receiver of the number of zone trips while in a disarmed state. The number of trips for
each zone set as trafc count are added together and included with the area closing
message and reported to the central station automation system. Default is NO.
13.20 Zone Audit Days
Enter the number of days (0 to 99) allowed to elapse without the zone being tripped
before a fault message is sent. The message is sent to the receiver(s) programmed
to receive Supervisory/Trouble Reports at 10:00 am following the expiration of the
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins
to countdown the number of days programmed. After the countdown expires, a fault
message is sent and the Zone Audit Days timer restarts and begins to countdown the
number of days programmed. Available for all zone types except re and re verify.
Enter 0 (zero) to disable this function. Default is 0 (zero).
13.21 Receiver Routing
This option displays if Zone Type is set for Auxiliary 1 or Auxiliary 2.
Press any top row key to select the Receiver Routing for the selected zone.
Select NORM to send Alarm and Supv/Trbl messages from this zone to receiver 1 or
receiver 2 as programmed within the receiver.
Select 1 to send Alarm and Supv/Trbl messages from this zone to receiver 1 only,
regardless of the programming for that receiver.
Select 2 to send Alarm and Supv/Trbl messages from this zone to receiver 2 only,
regardless of the programming for that receiver.
Select BOTH to send Alarm and Supv/Trbl messages from this zone to both
receivers, regardless of the programming for either receiver.
13.22 Zone Number
Enter the zone number you want to program next. Return to section 11.1 and follow the
descriptions of each programming option. If all zones are programmed, press the ARROW
key at the ZONE NO: – display to continue.
PRIORITY NO YES
TRAFFIC COUNT
ZONE AUDIT DAYS:
RECEIVER ROUTING
ZONE NO: -