9.16 House Code
When using a DMP wireless system, enter a house code between 1 and 50 for the
wireless system to use. The DMP wireless receiver automatically programs the house
code into the wireless transmitters when the unique transmitter serial number is
programmed into the panel. See Wireless programming in Zone Information. Default is 0
(zero) indicating the DMP wireless system is not being used.
The house code identies the panel, receiver, and transmitters to each other. When
operating, the receiver listens for transmissions that have the programmed house code
and transmitter serial number.
Note: The exibility of DMP two-way wireless operation allows an existing house code
to be changed in the panel at any time. The transmitter may take up to two minutes to
learn the new house code and continue operation.
Note: When any wireless zone programming is changed in the panel, wireless receiver
zone programming is updated by the panel. At that point, all wireless zones display as
normal for up to 1 minute, regardless of the actual state of the zone.
9.16.1 Detect Wireless Jamming
This option displays when the House Code entered is for a DMP 1100D Series Wireless
system. When enabled and the receiver detects jamming, a trouble or alarm message
is sent to the receiver and displays in the Status List. Select YES to enable jamming
messages to display in the Status List. Select NO to disable jamming messages.
Default is NO.
9.16.2 Wireless Audible Annunciation
This option displays when the House Code entered is for a DMP 1100D Series Wireless
system (1-50). Press any top row key to select the keypad buzzer annunciation method
for wireless low battery and missing messages.
Select ANY to enable annunciation anytime.
Select DAY to enable annunciation except during sleeping hours (9 PM to 9 AM).
Select MIN (minimum) to annunciate only Fire and Fire Verify zones during daytime hours
(9 AM to 9 PM). Default is DAY.
9.17 Built-In 1100 Wireless (XT50 only)
Select YES if using the built-in wireless receiver on the XT50. If selected, zones 80-
99 are available to be programmed as wireless zones in addition to any keypad zone
number. Select NO to use an external 1100 series wireless receiver. If NO is selected,
address 8 is usable with zones 81-84 for hardwire or wireless operation, but zones 80 and
85-99 are not available. Default is YES.
9.18 Enable Keypad Panic Keys
This option allows the two-button panic key operation selected at a keypad to send the
Panic, Emergency, or Fire message to the central station receiver. Select YES to enable
the two-button panic operation. To disable the two-button panic operation, select NO.
Default is YES.
9.19 Occupied Premises
Select YES to allow the panel to automatically disarm the interior area(s) when arming
all areas and a perimeter zone is not tripped during the exit delay.
This False Alarm Reduction feature will keep a user from arming the entire system when
they do not exit and remain in the premise. Select NO to not automatically disarm
interior area(s). Default is YES.
9.20 Use False Alarm Question
Select YES to display IS THIS A FALSE ALARM? NO YES at the keypad in place of CANCEL
VERIFY when a burglar alarm occurs. Default is YES.
9.21 Weather Zip Code
This option allows local U.S.A. weather updates to display on the keypad. Enter the zip
code of the user at this option. When no number is entered weather conditions are not
displayed. Default is 0 (zero).
If using a 7800 Series keypad, the current weather conditions and the next day’s forecast
display as graphics on the Main Screen. All other DMP keypads display the weather
information in the Status List.
HOUSE CODE: 0
DET JAMNG NO YES
WLS AUDIBLE: DAY
ANY DAY MIN
BUILT IN 1100
WIRELESS
NO
YES
KPD PANCS NO YES
OCCUPIED PREMISE
NO YES
USE FALSE ALARM
QUESTION? NO YES
ENTER WEATHER
ZIP CODE: 0
Zobrazit stránku 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 54 55

Komentáře k této Příručce

Žádné komentáře