Digital Monitoring Products XT Series Programming Guide
34
ZONE INFORMATION
14.10.11 Output Action
This option allows you to dene the output action (STD, PLS, MOM, TGL, OFF) for the
selected output number. The default is Steady.
STD (Steady) - The output is turned on and remains on.
PLS (Pulse) - The output alternates one second on and one second off.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the on state and off state. Each button
press toggles the output state.
OFF (Off) - The output is turned off. If programmed, the output was turned on by some
other means such as another button press, a zone action, or a schedule.
Note: When the output is assigned to PN/PN2 or EM/EM2 button action and is turned
on, the output turns off when any area is disarmed.
When the output action is steady, pulse or toggle and the output is turned on, the
output remains on until:
— the output cutoff time expires
— the output is reset from the keypad menu
— toggled off
Note: All wireless programming is stored in the XT30 or XT50 panel. When using the XT30, the 1100D,
1100DI, or 1100DH Wireless Receiver obtains the necessary programming information from the panel each
time the receiver powers up, when the programmer STOP routine is selected or the panel is reset. The
receiver memory refresh takes up to 45 seconds to complete depending on the number of wireless zones
programmed and the Red LED remains on during this time. Normal receiver operation is inhibited during
the memory refresh period.
14.11 Alarm Action
The Alarm Action section allows you to change or conrm the default alarm
characteristics of a zone type.
If you selected the non-24-hour zone type Blank, Night, Day, Exit, Auxiliary 1, or
Auxiliary 2, the Alarm Action programing begins with Disarmed Open.
If you selected the 24-hour zone type Fire, Panic, Emergency, or Supervisory, the Alarm
Action programming begins with Armed Open.
The Fire Verify zone type functions the same as Fire Type, with the following exceptions:
When a Fire Verify zone is placed into shorted condition, the panel performs a Sensor
Reset and does not send a report. If any Fire Verify or Fire zone initiates an alarm within
120 seconds after the reset, an alarm is indicated. If an alarm is initiated after 120
seconds, the cycle is repeated. If no other Fire Verify or Fire zone is alarmed within 120
seconds, a zone fault report is sent to the receiver.
14.12 Disarmed Open
Denes the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to dene:
• Message to Transmit
• Output/Favorite Number
• Output Action
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press the COMMAND key to continue.
ACTION:
STD PLS MOM TGL
OFF
ALARM ACTION . . .
DISARMED OPEN