OUTPUT OPTIONS
11.9 Begin Exit Output
This output/Favorite turns on any time an exit delay time starts. The output turns off
when the system arms or when the arming has been stopped. Enter 0 (zero) to disable.
11.10 End Exit Output
This output/Favorite turns on any time an exit delay time ends. The output turns off
when the system disarms. Enter 0 (zero) to disable.
11.11 Ready Output
This output/Favorite turns on whenever all disarmed zones are in a normal state. The
output turns off when any disarmed zone is in a bad state. Enter 0 (zero) to disable.
11.12 Armed Output
This output/Favorite turns on any time an area of the system is armed. The output turns
off when the system completely disarms. Enter 0 (zero) to disable this output.
Favorites:
For a Home/Away system:
When the system is armed AWAY, the programmed Favorite activates.
When the system is armed SLEEP, the programmed Favorite plus 1 is activated.
For example, If the Armed Output is F05, F06 activates when Sleep is armed.
When the system is armed HOME, the programmed Favorite plus 2 is activated. For
example, If the Armed Output is F05, F07 activates when Home is armed.
For an All/Perimeter system:
When the system is armed ALL, the programmed Favorite activates.
When the system is armed PERIMETER, the programmed Favorite plus 1 is activated.
For example, If the Armed Output is F05, F06 activates when Perimeter is armed.
For an Area system:
When any area of the system is armed, the programmed Favorite activates.
11.13 Disarmed Output
This output/Favorite turns on when all areas of the panel are disarmed. The output
turns off when an area is armed.
11.14 Burglary Output
This output/Favorite turns on any time a burglary zone goes into alarm. The output
turns off when the area in which the alarm occurred disarms and no other burglary zones
are in alarm. Enter 0 (zero) to disable this output.
11.15 Late To Close Output
Enter the output/Favorite to turn on at the expiration of a closing schedule when all
areas are not armed. The output activates simultaneously with the CLOSING TIME!
keypad display. The output is turned off when all areas are armed, the closing is
extended, or the schedule is changed.
11.16 Arm-Alarm Output
Enter the output/Favorite to turn on steady when any area of the system is armed. If
an alarm occurs causing the keypads to turn Red, this output pulses and continues to
pulse for approximately three (3) minutes after the panel is disarmed. Enter 0 (zero) to
disable.
Wireless Outputs
The Arm-Alarm Output is compatible with the Model 1117 Wireless LED
Annunciator and the Model 1116 Wireless Relay Output connected to a Model
572 Indicator LED.
When the Model 1117 is battery operated, the LED is off when the system is
armed to conserve battery life. If an alarm occurs, the output ashes quickly.
using the Model 1116 connected to a Model 572, the LED is on when the system
is armed. If an alarm occurs, the output pulses.
To operate the Arm-Alarm output within one second, program a fast response
number from 41 to 44. Fast response operation reduces overall wireless output
battery life.
To operate the Arm-Alarm output within 15 seconds, program a slow response
number from 31 to 34. Slow response operation increases overall wireless
output battery life.
BEGIN EXIT: 0
END EXIT: 0
READY OUT: 0
ARMED OUT: 0
DISARMED OUT: 0
BURGLARY OUT: 0
LATE CLS OUT: 0
ARM-ALARM OUT: 0