Digital Monitoring Products XR100 Series Programming Guide
12
CommuniCation
3.27
SPV/TRBL YES
Supervisory/Trouble Reports
This option displays when the Path Type is Primary. All backup paths within the
groupfollowthesameprogrammingforSupervisory/TroubleReports.DefaultisYes.
NO YES FIRE
WhenYESisselected,thefollowingreportsaresentforallzonetypes:
•Trouble •LowBattery •Missing •Fault
•Restorals •SystemTroubles •SystemRestoral
WhenFIREisselected,thefollowingreportsaresentforFire,FireVerify,and
SupervisoryZones:
•Trouble •LowBattery •Missing •Fault
•Restorals •SystemTroubles •SystemRestoral
ServicemanreportsaresentregardlessoftheselectionmadeforSupervisory/
Trouble reports.
3.28
O/C USER NO YES
Opening/Closing and User Reports
This option displays when the Path Type is Primary. All backup paths within the
groupfollowthesameprogrammingforOpening/ClosingandUserReports.Default
is Yes.
WhenYESisselected,thefollowingreportsbyuseraresenttothisreceiver.
•Opening •Codechanges(includingadding,deleting,changing)
•Closing •Schedulechanges(temporary,permanent,shift)
•Bypass •Holidaydatechanges
•Reset
3.29
DOOR ACS YES
Door Access Report
This option displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Door Access Reports. Default is Deny.
NO YES DENY
SelectYEStoenableDoorAccessGrantedandDeniedreportstothisreceiver
wheneveradooraccessisgrantedtoauser.TheDoorAccessGrantedreportis
only sent if the keypad number has also been selected in Access Keypads under the
SYSTEM REPORTS programming.
SelectDENYtoenableDoorAccessDeniedreportsonlytothisreceiverwhenadoor
access is denied to a user.
3.30
SEND COMM TRBL:
Send Communication Trouble
NO YES
This option displays for each path and determines if and how communication
trouble on the path is sent to the receiver. A trouble message indicates both the
path number and communication type that failed. Default is Yes.
3.31
SEND PATH INFO:
Send Path Information
NO YES
ThisoptiondisplaysforeachpathandifYES,eachpanelmessageincludespath
information such as path number, communication type, and path type. Default is
No.