Digital Monitoring Products XR100 Series Programming Guide
44
AreA InformAtIon
17.12
AUTO ARM NO YES
Automatic Arming
SelectYEStoallowthisareatoarmautomaticallyaccordingtopermanent,
temporary, or extended schedules. If no schedules are programmed, the area auto
arms every hour.
IfclosingcheckisselectedasYES,theautomaticarmingfunctiondoesnottake
place until the expiration of a ten minute Closing Check delay. See Closing Check. If
the area has been disarmed outside of any permanent or temporary schedule, the
closing check sequence occurs one hour after the area is disarmed.
At arming, bad zones are handled according to the option selected in section Bad
Zones.Ifaclosingreportissent,theusernumberisindicatedasSCHontheSCS-1R
Receiver. NO disables automatic arming for this area.
Note: For ANSI/SIA CP-01 UL installations, Automatic Arming cannot be used for
arming.
17.13
BAD ZONES: BYP
Bad Zones
At the time of automatic arming, some zones in the area may not be in a normal
condition. This option allows you to program the panel response to these bad
zones.ThisoptiondoesnotdisplayifAUTOARMisNO.
BYP FORC REF
BYP - All bad zones are bypassed. A report of the bypass is sent to the receiver if
BypassReportsisYES.ThereportindicatesSCHastheusernumber.
FORC - Allbadzonesareforcearmed.Zonesforcearmedinabadconditionare
capable of restoring and reporting an alarm if tripped. A forced zone report is
transmittedifBypassReportsisYES.ThereportindicatesSCHastheusernumber.
REF - The automatic arming is refused and no arming takes place. A No Closing
report is sent to the receiver regardless of the Closing Check selection.
17.14
AUTO DIS NO YES
Automatic Disarming
NOdisablesautomaticdisarmingbyscheduleforthisarea.WhenYESisselected,
the area automatically disarms according to permanent or temporary schedules. If
an opening report is sent to the receiver, the user number is indicated as SCH.
Note: For ANSI/SIA CP-01 UL installations, Automatic Disarming cannot be used
for disarming.
17.15
ARMED OUTPUT: 0
Armed Output Number
Entertheoutputtoturnonwhenthisareaisarmed.Ifanexitdelayisusedforthis
area, the Armed Output turns on at the start of the exit delay. The output is turned
offwhenthisareaisdisarmed.TheoutputcannotbeturnedonfromtheUserMenu
OutputsOn/Offoption.
17.16
LATE OUTPUT: 0
Late Output Number
Entertheoutputtoturnonwhenthisareaisnotarmedbyitsscheduledtime
andAreaLateorClosingTimedisplaysatakeypadandthekeypadbuzzerison.
The output is turned off when the keypad buzzer is silenced by pressing any key.
Defaultis0(zero).
17.17
LATE/ARM DLY: 60
Late Arm Delay
Enter4to250minutestodelaybeforeautomaticre-armingoccursafterthearea
becomesdisarmedoutsideofschedules.SeeClosingCheck.Defaultis60minutes.
Note:TheLateArmDelaycanbesupersededbytheReArmDelaysettingofthe
UserProleassignedtotheuserwhodisarmedthearea.RefertotheReArmDelay
sectionintheXR100SeriesUser’sGuide(LT-0683).