21.4 Using the Walk Test
The XR100 Series panel provides a walk test feature that allows a single technician to test the protection
devicesconnectedtozonesonthesystem.ConducttheWalkTestwithin30minutesofresettingthepanel.
TheWalkTestautomaticallyendsifnozonesaretrippedfor20minutes.TESTINPROGRESSdisplaysatall
keypadsprogrammedwiththesameAreaDisplayfeatures.Whenveminutesremain,TESTENDWARNING
displays. The Walk Test only tests zones assigned to the areas programmed into the keypad in Area Display.
IfanyareasarearmedtheWalkTestdoesnotstartandSYSTEMARMEDdisplays.
Note:IfthePanicSupervisionoptionisenabledinSYSTEMOPTIONS,thepanicbuttononanyprogrammed
keyfobcanbetestedduringtheWalkTest.Whenthepanicbuttonispressedavericationmessageissent
by the receiver.
WALK TEST
Walk Test
To conduct the Walk Test, reset the control panel by momentarily placing a
jumperonJ16.Fromthekeypad,enterthecode8144andpressCOMMAND.The
keypaddisplaysWALKTESTforfourseconds.Ifthesystemismonitoredandthe
communicationtypeisDDorNET,thesystemsendsaSystemTestBeginreportto
the central station. After four seconds, the keypad displays the zone type choices
for testing.
*BG *FI *PN *SV
Zone Types
Select the zone type you want to test. An asterisk next to the zone type indicates the
zone type chosen for testing. Press the Select key again to deselect the zone type.
When you have selected all the zone types you want for testing, press the COMMAND
key to display the next Walk Test option. Pressing the Back Arrow key exits the Walk
Test.
BG(Burglaryzones)-SelectBGtotestburglaryzones.IncludesallNT,DY,EX,A1,
andA2zones.
FI(Firezones)-SelectFItotestrezones.IncludesallFIandFVzones.
PN(Paniczones)-SelectPNtotestpaniczones.IncludesallPNandEMzones.
You do NOT havetoholdthezonesfor2secondsinnormalmode.Youareonly
required to hold the panic during the Walk Test because the zone takes additional
time to report when the system is in test mode.
SV(Supervisoryzones)-SelectSVtotestsupervisoryzones.IncludesallSVzones.
Note: During the Walk Test, trip each zone device or button on the system for 1 to
2seconds.
WLS PIR
WLS(WirelessCheck-inTest)-SelectWLStoautomaticallytestwirelesstransmitter
communications. Includes all wireless devices except key fobs and transmitters
programmedforasupervisiontimeof0(zero).
PIR(WirelessPIRWalkTest)-ThePIRWalkTestallowstheinstallertoverifythe
1126operation.Whenenabled,the1126LEDasheseachtimemotionisdetected
forupto30minutes.Thisisalocaltestonlyandnomessagesaresenttothe
Central Station.
BELL NO YES
Bell Action
This option selects the bell output action when a zone under test faults. This option
allowsthepanelbell,and/orburglarybell,and/orrebelltoturnONandthen
OFFeachtimeazoneistripped(openedorshorted).
NO - Select NO for no bell output action during Walk Test.
YES - SelectYEStoturnonanybelloutputfor2secondsduringWalkTest.
PULS -SelectPULStoturnonanybelloutputfor1/4secondduringWalkTest.Any
LX-Busdeviceoutputturnsonfor1.6secondsduetothepollingcycle.
TRIPS: XXX END
Trip Counter For Walk Test
Once in the Walk Test, walk around and trip each protective device. Continue
tripping devices until the entire system is tested.