XR100 Series Programming Guide Digital Monitoring Products
27
SyStem OptiOnS
9.5
ENTRY DLY 2: 60
ENTRY DLY 3: 90
ENTRY DLY 1: 30
ENTRY DLY 4: 120
Entry Delay 1
EntertheEntryDelaytimeforallExittypezonesprogrammedtouseEntryDelay
1.WhenanarmedExittypezoneisfaulted,thekeypadprewarntonebegins
sounding.AllkeypadsprogrammedtoprewarnforthatzonedisplayENTERCODE:-
andthenameofthezonecausingtheentrydelay.Whentherstdigitofacodeis
entered, the prewarn tone stops at that keypad. If an invalid code is entered, the
prewarn tone begins sounding again. The area must be disarmed before the delay
expires or an alarm report is sent to the receiver and an alarm sounds. All zones in
thatareaaredelayedalongwiththeExitzone.EntryDelaytimescanbefrom30to
250seconds.Repeattheaboveforeachentrydelaybeingusedinthesystem.
Note:SpecicExitErroroperationisbasedontheEntryDelayused(1-4)withan
EXtypezone.SeeExitDelay.
Note: For UL Installations, the combined Transmit Delay (Abort Window) and
Entry Delay must not exceed one (1) minute.
9.6
CRS ZONE TM: 4
Cross Zone Time
Enterthetimeallowedbetweenzonefaults.Whenzonesarecrosszoned,the
same zone or a second cross zoned zone must fault within this time in order for
an alarm report for both zones to be sent to the receiver. If the cross zone time
expireswithoutthesecondzonefaulting,onlyazonefaultfromtherstzoneis
reported.Cross-zonetimecanbefrom4to250seconds.Entering0(zero)disables
this function. Default is 4. See the Appendix.
9.7
RETARD DELAY: 10
Zone Retard Delay
EntertheretardtimeassignedtoFire,Supervisory,Auxiliary1,Auxiliary2,
Arming, and Panic type zones. The retard delay only functions when the zone is
shorted. The zone must remain shorted for the entire length of the Retard Delay
beforebeingrecognizedbythepanel.TheZoneRetardDelaycanbefrom1to250
seconds.Enteringa0(zero)disablesthisfunction.
9.8
PWR FAIL HRS: 1
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off
for the length of the programmed delay time, an AC power failure report is sent to
thereceiver.Thedelaytimecanbefrom1to15hours.Enteringa0(zero)sends
thepowerfailurereportaftera15-seconddelay.Thedefaultsettingis1.
Note: For UL burglary installations Power Fail Delay shall be programmed to 0
(zero).
Note: For UL re installations, Power Fail Delay shall be programmed as
required by the service of the panel. For Central Station service: 6-12, for
Remote Station service: 12-15.
9.9
SWGRBYPS TRIPS: 2
Swinger Bypass Trips
Enterthenumberoftimes(1-6)azonecangointoanalarmortroublecondition
within one hour be fore being auto matically bypassed. You can select one or two
trips. Bypassed zones are auto matically reset when the area they are assigned to
isdisarmed.All24-hourzonesareresetwhenanyareaofthesystemisdisarmed.
AprogrammingStopoperationrestoresabypassedzone.Entering0(zero)disables
thisfunction.Defaultis2.
How it works
Thepanelhourtimerstartsat59minutespastthehour.Ifthehourtimerexpires
beforethetripcounterisexceeded,thetripcounterreturnsto0(zero).Ifthetrip
counter is exceeded before the hour expires, the zone is auto matically bypassed by
thepanel.ABypassReportissenttothereceiverifBypassReportsisYES.
Note: Not investigated by UL.